How to see real time values in an ION meter’s advanced module registers?
Issue
A user may require seeing real time values in an ION module registers.
Product line
ION Setup
Environment
ION Setup
Cause
A user may require seeing real time values in the advanced ION module registers, instead of updating the values by re-clicking on the register tabs.
Resolution
In ION Setup:
- Switch to advanced mode by holding down the Ctrl and left clicking on the mouse.
- Open the desired module folder, and navigate to the module.
- If prompted enter the meter’s password.
- Hold shift and left click on the Output Registers tab. This will switch the module into value mode.
- By default, the registers are set to update by click only.
- To change this right-click on the Output Registers tab and select the desired update interval. Available options are every second, 5 seconds, 10 seconds, and 30 Seconds.