PME 9.0 - Web Application - Diagrams - "There was a problem processing you request"
Power Monitoring Expert 9.0
Enviroment
Digramas/DatalogViewer - Web Application
Issue
When attempting to open a diagram in Web Application the system gives an error: "There was a problem processing you request"
Issue 1
Error opening a Diagram
It can be another IonName.[Language].resx file as well.
Cause
This was probably an upgraded system where the diagram link was referencing an existing resx file that in the current version has been renamed or does not exist anymore.
Resolution
Navigate to C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\system\etc
Search for IONNames.[LANGUAGE_DESIRED].resx
Make a copy of it
Always keep the original in the folder
Rename the copy to match the file name that the error is claiming that could not be found
IIS reset and refresh the Web Page
Issue 2
Error opening a Datalog Viewer
Error in: https://wasg00115/ion/Historical/DisplayLogs.aspx?queryId=8a2a27f8-a578-43bf-9b3c-cb49a19cdef6&dgm=x-pml:/diagrams/ud/default/PM820_FAC-4WYE_V1.1.5/PM820_FAC-4WYE_V1.1.5-rev.dgm&node=HUB-L4.PM-MSB-INC&logServerName=QUERYSERVER.TNETVMPME9&logServerHandle=327952&isEventLog=
Error Message: An error occurred in GetConnectionStringFromQueryServer calling method lsSetupObject.GetConnectionString while attempting to access Query Server [QUERYSERVER.OLD_SERVER_NAME] with handle [327952].<br>With moniker: pmlitem:QUERYSERVER.TNETVMPME9:pmlnew:PMLQueryServer.IONModuleInfo:<br><br>The Query Server may not be running.<br>
Stack Trace: at WebReach.Historical.MapPegQueryToSQL.GetConnectionStringFromQueryServer(String lsSoftwareNode, String lsHandle)
at WebReach.Historical.MapPegQueryToSQL.Execute(Int32 numRecordsToGet, String dgm, String node, String queryId, String isEventLog, String logServerName, String logServerHandle, String whereClause)
at WebReach.Historical.MapPegQueryToSQL.Execute(Int32 numRecordsToGet, NameValueCollection args)
at WebReach.Historical.DisplayLogs.Page_Load(Object sender, EventArgs e)
at System.Web.Util.CalliEventHandlerDelegateProxy.Callback(Object sender, EventArgs e)
at System.Web.UI.Control.OnLoad(EventArgs e)
at System.Web.UI.Control.LoadRecursive()
at System.Web.UI.Page.ProcessRequestMain(Boolean includeStagesBeforeAsyncPoint, Boolean includeStagesAfterAsyncPoint)
Cause
This issue happens when the device icons are pasted in custom diagrams and query server is not properly set in the custom vista diagram pages. When check the url when a meter template is opened you can see the query server name weater it is properly passe or not -
https://wasg00115/ion/default.aspx?dgm=x-pml:/diagrams/ud/default/PM820_FAC-4WYE_V1.1.5/PM820_FAC-4WYE_V1.1.5-rev.dgm&node=HUB-L4.PM-MSB-INC&logServerName=QUERYSERVER.OLD_SERVER_NAME&logServerHandle=327952
in this case the URL is pointing to wrong query server.
Resolution
Open the diagram in Vista and right click on page > Properties > Query server > Select 'custom query server' > click on "Edit Link" button > and select the local PME query server.
Restat 'ION Application Modules Core Services Host' service and refresh the browser
Diterbitkan untuk: Schneider Electric Indonesia
Perlu bantuan?
Pemilih produk
Temukan produk dan aksesoris yang tepat untuk aplikasi Anda secara cepat dan mudah.
Dapatkan Penawaran Harga
Silakan kirimkan pertanyaan terkait penjualan secara online dan pakar kami akan menghubungi Anda.
Tempat pembelian
Temukan distributor Schneider Electric terdekat di lokasi Anda dengan mudah.
Pusat Bantuan
Temukan sumber daya dukungan untuk seluruh kebutuhan Anda, di satu tempat.