What causes an overcurrent OCF fault on the ATV12?

Issue:
Getting a overcurrent OCF fault on ATV12

Product Line:
Altivar Machine, ATV12

Environment:
All serial numbers

Cause:
• Parameters in the Motor control menu drC- page 57 are not correct
• Inertia or load too high
• Mechanical locking

Resolution:
• Check the parameters
• Check the size of the motor/drive/load
• Check the state of the mechanism
• Connect line chokes
• Reduce the Switching frequency SFr page 59
• Check the ground connection of drive, motor cable and motor insulation

ATV12 user manual:
https://www.se.com/ww/en/download/document/BBV28581/