{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

ACOA5XX cooling failure

Issue:
This dcoument describes the issues that can cause an ACOA5XX cooling failure.

Product line:
ACOA5XX.

Environment:
All Serial Numbers.

Cause:
Supply Air Temperature> 90 F and Cooling Output < 4 kW.

Resolution:

Supply Air Temperature> 90 F and Cooling Output < 4 kW

OA will shut down

OA will restart after 5 Min

If conditions still exists after 60 seconds OA will shut down.

tf = 300oF* sec/ tsup - 90oF

Where

Tsup is the average supply air temperature in oF

Schneider Electric Ireland

Attachment(s)

ACOA5XX cooling failure.pdfACOA5XX cooling failure.pdf [205.17 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: