PSO (Power SCADA Operation) IO Server crashes while communicating on ION protocol with ION meters.

This is because the current driver driver does not handle frameworks with gaps in recorders properly. To fix the issue we have following workaround. Please correct template of all ION meters as follows using latest ION Setup.

  • Open Advanced Configuration Mode for the meter to be edited
  • Navigate to Data Rec Module > EgyDmd
  • The Energy Demand log is configured to use Sources 8,9,10, As by default it uses Sources 1,2,3
  • Edit the Inputs and change the Inputs to use Sources 1,2 and 3.
  • This must be done for all ION meters communicating to PSO over ION protocol
  • See attached PDF for detailed description for the same.

שניידר אלקטריק ישראל

קבצים מצורפים
IO Server crashes while communicating on ION protocol with ION meters.pdf [116.8 KB]
גלה עוד
טווח:
גלה עוד
טווח:

זקוק לעזרה?

  • בורר מוצרים

    חפשו ברשת מפיצים מאומתים עם יותר מ-15,000 נקודות מכירה ברחבי העולם.

  • קבלת הצעת מחיר

    התחילו את בקשת הקניה בצורה מקוונת ונציג מכירות ייצור עמכם קשר.

  • היכן לקנות?

    אתר בקלות את מפיץ Schneider Electric הקרוב ביותר אליך.

  • מרכז העזרה

    חפשו משאבי תמיכה לכל הצרכים שלכם במקום אחד.

  • תיעוד מוצרים
  • בורר המוצר
  • מוצרים חלופיים והחלפה
  • מרכז עזרה ויצירת קשר
  • איתור סניפי שניידר אלקטריק
  • היכן לקנות
  • משרות
  • פרופיל חברה
  • דיווח על התנהגות בלתי הולמת
  • נגישות
  • חדר חדשות
  • משקיעים
  • EcoStruxure
  • חיפוש משימה
  • בלוג
  • מדיניות שמירה על פרטיות
  • הודעה על קובצי Cookie
  • תנאי שימוש
  • Change your cookie settings