Come possiamo aiutarti oggi?

In un Altivar 320 come posso leggere da un protocollo di comunicazione l'ultimo difetto rilevato dal drive?

Per leggere l'ultimo difetto rilevato dall'Altivar 320 tramite protocollo di comunicazione è possibile leggere la variabile Last fault occurred [LFT]

la variabile ha la seguente corrispondenza Valore->Difetto

0 [No fault] (NOF) No fault saved

2 [Control Eeprom] (EEF1) EEprom control fault

3 [Incorrect config.] (CFF) Incorrect configuration

4 [Invalid config.] (CFI) Invalid config parameters

5 [Modbus com.] (SLF1) Modbus coms fault

6 [int. com.link] (ILF) Com Internal link fault

7 [Com. network] (CNF) Network fault

8 [External flt-LI/Bit] (EPF1) External fault logic input

9 [Overcurrent] (OCF) Overcurrent fault

10 [Precharge] (CRF1) Precharge

11 [Speed fdback loss] (SPF) Speed feedback loss

12 [Load slipping] (ANF) Output speed <> ref

16 [Drive overheat] (OHF) Drive overheating fault

17 [Motor overload] (OLF) Motor overload fault

18 [Overbraking] (OBF) DC bus overvoltage fault

19 [Mains overvoltage] (OSF) Supply overvoltage fault

20 [1 output phase loss] (OPF1) 1 motor phase loss fault

21 [Input phase loss] (PHF) Supply phase loss fault

22 [Undervoltage] (USF) Supply undervoltage fault

23 [Motor short circuit] (SCF1) Motor short circuit

24 [Overspeed] (SOF) Motor overspeed fault

25 [Auto-tuning ] (TNF) Auto-tuning fault

26 [Rating error] (INF1) Rating error

27 [PWR Calib.] (INF2) Incompatible control card

28 [Int.serial link] (INF3) Internal coms link fault

29 [Int.Mfg area] (INF4) Internal manu zone fault

30 [Power Eeprom] (EEF2) EEprom power fault

32 [Ground short circuit] (SCF3) Ground short circuit

33 [3out ph loss] (OPF2) 3 motor phase loss fault

34 [CAN com.] (COF) Comms fault CANopen

35 [Brake control] (BLF) Brake control fault

38 [External fault com.] (EPF2) External fault comms

41 [Brake feedback] (BRF) Brake feedback fault

42 [PC com.] (SLF2) PC coms fault

44 [Torque/current lim] (SSF) Torque/current limit fault

45 [HMI com.] (SLF3) HMI coms fault

49 [LI6=PTC probe] (PTFL) LI6=PTC failed

50 [PTC fault] (OTFL) LI6=PTC overheat fault

51 [Internal- I measure] (INF9) Internal I measure fault

52 [Internal-mains circuit] (INFA) Internal i/p volt circuit flt

53 [Internal- th. sensor] (INFB) Internal temperature fault

54 [IGBT overheat] (TJF) IGBT overheat fault

55 [IGBT short circuit] (SCF4) IGBT short circuit fault

56 [Motor short circuit] (SCF5) motor short circuit

58 [Out. contact. stuck] (FCF1) Output cont close fault

59 [Out. contact. open.] (FCF2) Output cont open fault

64 [input contactor] (LCF) input contactor

67 [IGBT desaturation] (HDF) IGBT desaturation

68 [Internal-option] (INF6) Internal option fault

69 [internal- CPU ] (INFE) internal- CPU

71 [AI3 4-20mA loss] (LFF3) AI3 4-20mA loss

73 [Cards pairing] (HCF) Cards pairing

76 [Load fault] (DLF) Dynamic load fault

77 [Bad conf] (CFI2) Interrupted config.

99 [Ch.sw. fault] (CSF) Channel switching fault

100 [Pr.Underload.Flt] (ULF) Process Underlaod Fault

101 [Proc.Overload Flt] (OLC) Process Overload Fault

105 [Angle error] (ASF) Angle error

107 [Safety fault] (SAFF) Safety fault

108 [FB fault] (FBE) FB fault

109 [FB stop flt.] (FBES) FB stop fault

Schneider Electric Italy

  • Documentazione prodotti
  • Software scaricabili
  • Selettore prodotto
  • Sostituzione del prodotto
  • Supporto Guidato e Contact Center
  • Trova i nostri uffici
  • Ottieni un preventivo
  • Dove acquistare
  • Comunità di Schneider Electric
  • Carriere
  • Lavora con noi
  • Profilo aziendale
  • Segnala una cattiva condotta
  • Accessibilità
  • Newsroom
  • Investitori
  • EcoStruxure
  • Blog
  • Informativa privacy
  • Informativa sui cookie
  • Note legali
  • Change your cookie settings