ION Setup interface cannot scroll horizontal far enough to view all data.
Issue
ION Setup interface cannot scroll far enough to view all data.


Product Line
ION Setup 3.0
ION Setup 2.2

Environment
Windows 7

Cause
There is a bug in Windows 7 where in, if you have a high resolution screen at install time, Win7 will install a larger font set (125%) by default. If you then choose go back to the standard font size (100%), Windows will keep some of the large fonts even though everything else is adjusted for standard fonts, causing programs that use these fonts to break because the text will not always fit inside the Interface.

Resolution
*Warning: This article contains information about editing the registry. Improper changes to the registry can permanently damage the operating system. Always backup the registry before making any changes.*


By editing the Windows registry you can get the original, intended fonts back:

1) Open the start menu and type regedit and then press Enter.

2) Locate the key HKEY_LOCAL_MACHINE\SOFTWARE\Microsoft\Windows NT\CurrentVersion\Fonts

3) Find the value MS Sans Serif 8,10,12,14,18,24

4) Change from SSERIFF.FON to SSERIFE.FON

5) Find MS Serif 8,10,12,14,18,24

6) Change from SERIFF.FON to SERIFE.FON

7) Finally find Courier 10,12,15

8) Change from COURF.FON to COURE.FON

9)  Restart your system in order for the changes to take effect!



The exact font names may vary depending on locale settings. Use these tables for reference: Column on the left is the key found in Registry, column on the right is the value to change to.

MS Sans Serif 8,10,12,14,18,24
SSERIFF.FON         SSERIFE.FON
SSERIFFE.FON      SSERIFEE.FON
SSERIFFG.FON      SSERIFEG.FON
SSERIFFR.FON      SSERIFER.FON
SSERIFFT.FON      SSERIFET.FON
SSEF1255.FON      SSEE1255.FON
SSEF1256.FON      SSEE1256.FON
SSEF1257.FON      SSEE1257.FON
SSEF874.FON        SSEE874.FON

MS Serif 8,10,12,14,18,24
SERIFF.FON        SERIFE.FON
SERIFFE.FON      SERIFEE.FON
SERIFFG.FON      SERIFEG.FON
SERIFFR.FON      SERIFER.FON
SERIFFT.FON      SERIFET.FON
SERF1255.FON  SERE1255.FON
SERF1256.FON  SERE1256.FON
SERF1257.FON  SERE1257.FON

Courier 10,12,15
COURF.FON          COURE.FON
COURFE.FON       COUREE.FON
COURFG.FON       COUREG.FON
COURFR.FON       COURER.FON
COURFT.FON        COURET.FON
COUF1255.FON    COUE1255.FON
COUF1256.FON    COUE1256.FON
COUF1257.FON    COUE1257.FON

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

  • 제품 선택기

    애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

  • 견적 받기

    영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

  • 구매처

    해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

  • 지원 센터

    한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings