StruxureWare Power Monitoring Expert (PME) 7.2 Web Reporter stop working after upgrading to Google Chrome 40
Issue:
The latest release of Chrome from Google (version 40.0.2214.91 m) blocks all plug-ins by default

Product Line:
Power Monitoring Expert 7.2.x
Power Monitoring Expert 8.x

Environment:
Chrome 40+
Power Monitoring Expert 7.2.x
Power Monitoring Expert 8.0
Power Monitoring Expert Software Web Applications

Cause:
The Web Applications in PME require a Silverlight plug-in which is blocked by default by this release of Chrome.

Resolution:
The following will be displayed when a user navigates to the PME Web Applications in this new version of Chrome:



To get the web page to load properly, you'll need to allow the Silverlight plug-in to run. To do so, you can click on the little "puzzle piece" with the red X on it that appears in the address bar. From there, you'll see an option to always allow plug-ins, as in the screenshot below:



To get the web page to load properly, the user need to allow the Silverlight plug-in to run. To do so, you can click on the little "puzzle piece" with the red X on it that appears in the address bar. From there, you'll see an option to always allow plug-ins, as in the screenshot below:



If you're still experiencing issues with Source and Measurement selector in the Reports tab after you're logged in, please follow the workaround provided in FA235076.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings