ieocr-mme 제품을 설치 중인데 설정에 따라 TRIP 접점을 어떻게 구성해야 하는지요?

mme 제품의 경우 SYScF 메뉴에 out 설정과 oP 설정에 따라 trip시 출력이 변경 됩니다.



아래 표를 참조 부탁 드립니다.
Non ZCT Type : MMED
Built in : MMEB
External ZCT : MMEZ

TypeOutputFunctionReadyRun(Y)Run(D)StopAlarmFaultFault Reset
Non ZCT Type- DOLO1ControlOpenCloseOpenCloseOpenOpen
O2ALo “A”OpenCloseOpenCloseOpenOpen
ALo “F”OpenCloseOpenFlicker*1Flicker IIOpen
ALo “H”OpenOpenOpenCloseOpenOpen
O3TripOpenOpenOpenOpenClose@OLOpen
Non ZCT Type- YDO1ControlOpenCloseOpenOpenOpenOpen
O2ControlOpenOpenCloseOpenOpenOpen
O3TripOpenOpenOpenOpenCloseOpen
Built in or External ZCT – DOL with COO1ControlOpenCloseOpenCloseOpenOpen
O2ALo “A”OpenCloseOpenCloseOpenOpen
ALo “F”OpenCloseOpenFlicker*1Flicker IIOpen
ALo “H”OpenOpenOpenCloseOpenOpen
O3TripOpenOpenOpenOpenCloseOpen
Built in or External ZCT – DOL with SEO1ControlOpenCloseOpenOpenOpen
O2OL TripOpenOpenOpenClose@OLOpen
O3EF TripOpenOpenOpenClose@EFOpen
Built in or External ZCT –  YD with COO1ControlOpenCloseOpenOpenOpenOpen
O2ControlOpenOpenCloseOpenOpenOpen
O3TripOpenOpenOpenOpenCloseOpen
Built in or External ZCT – YD with SEO1ControlOpenCloseOpenOpenOpenOpen
O2ControlOpenOpenCloseOpenOpenOpen
O3EF TripOpenOpenOpenOpenClose@EFOpen
Non ZCT Type InverterO1InverterOpenCloseOpenOpenOpen
O2N/AOpenOpenOpenOpenOpen
O3TripOpenOpenOpenCloseOpen
Non ZCT Type BypassO1N/AOpenOpenOpenOpenOpen
O2BypassOpenCloseOpenOpenOpen
O3TripOpenOpenOpenCloseOpen
Built in or External ZCT – Inverter  with COO1InverterOpenCloseOpenOpenOpen
O2N/AOpenOpenOpenOpenOpen
O3TripOpenOpenOpenCloseOpen
Built in or External ZCT – Inverter  with SEO1InverterOpenCloseOpenOpenOpen
O2N/AOpenOpenOpenOpenOpen
O3EF TripOpenOpenOpenClose@EFOpen
Built in or External ZCT – Bypass  with COO1N/AOpenOpenOpenOpenOpen
O2BypassOpenCloseOpenOpenOpen
O3TripOpenOpenOpenCloseOpen
Built in or External ZCT – Bypass  with SEO1N/AOpenOpenOpenOpenOpen
O2BypassOpenCloseOpenOpenOpen
O3EF TripOpenOpenOpenClose@EFOpen