브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
PSO (Power SCADA Operation) IO Server crashes while communicating on ION protocol with ION meters.

This is because the current driver driver does not handle frameworks with gaps in recorders properly. To fix the issue we have following workaround. Please correct template of all ION meters as follows using latest ION Setup.

  • Open Advanced Configuration Mode for the meter to be edited
  • Navigate to Data Rec Module > EgyDmd
  • The Energy Demand log is configured to use Sources 8,9,10, As by default it uses Sources 1,2,3
  • Edit the Inputs and change the Inputs to use Sources 1,2 and 3.
  • This must be done for all ION meters communicating to PSO over ION protocol
  • See attached PDF for detailed description for the same.

슈나이더 일렉트릭 Korea

첨부 파일
IO Server crashes while communicating on ION protocol with ION meters.pdf [116.8 KB]
자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings