Should the mounting rails of a sliding shelf be extended or retracted from the factory setting?

Issue:
Customers may want to retract or extend the rails of a sliding shelf.

Product Line:
NetShelter Sliding Shelves

Environment:
All versions and serial ranges.

Cause:
Rails may want to be extended or retracted to match where the rear mounting rails are installed.

Resolution:

The mounting rails of any sliding shelf should never be extended beyond the factory setting. Doing so will reduce the weight capacity of the sliding shelf.