undefined undefined
{}

Наши бренды

Impact-Company-Logo-English Black-01-177x54

Добро пожаловать на сайт Schneider Electric

Добро пожаловать на наш сайт.
Чем мы можем помочь сегодня?
Which registers hold the TMC2 analog cartridge status information in an M221 controller?

Issue
Which registers hold the TMC2 analog cartridge status information in an M221 controller?

Product Line
Modicon M221

Environment
EcoStruxure Machine Expert Basic / SoMachine Basic - PLC configuration software

Resolution
The status/diagnostic information for TMC2 analog cartridges is held in one dedicated address per channel.
For inputs, the syntax is: %IWS0.x0y
For outputs, the syntax is: %QWS0.x0y
where x is the cartridge number, and y is the channel number in the cartridge.

For example if we have a TM221C40T (which can physically accommodate two cartridges) with TMC2AI2 and TMC2AQ2C modules, there are 4 addresses containing the statuses of each of the 4 channels:

First cartridge (TMC2AI2 - analog input):
%IWS0.100: first cartridge, channel 1
%IWS0.101: first cartridge, channel 2

Second cartridge (TMC2AQ2C - current analog output)
%QWS0.200: second cartridge, channel 1
%QWS0.201: second cartridge, channel 2

For further information on programming, refer to the following documents:
EcoStruxure Machine Expert, Programming Guide
Modicon TMC2 Cartridges, Programming Guide

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Казахстан

Узнайте больше
Линейка:
Статьи, которые могут оказаться полезными
Узнайте больше
Линейка: