Issue:
ATV312 setup for auto, manual control
Product Line:
ATV312
Environment:
All
Cause:
Want to set up an 3 position switch for HOA control.
Resolution:
CTL menu
Fr1 = Ai1
Fr2 = AI3
RFC = LI3
You will need to also turn off preset speeds:
FUN menu
PSS
PS4 set to no
PS2 set to no
ATV312 setup for auto, manual control
Product Line:
ATV312
Environment:
All
Cause:
Want to set up an 3 position switch for HOA control.
Resolution:
CTL menu
Fr1 = Ai1
Fr2 = AI3
RFC = LI3
You will need to also turn off preset speeds:
FUN menu
PSS
PS4 set to no
PS2 set to no
Опубликовано для:Schneider Electric Казахстан

