Issue:
Possible causes for an ATV66 drives to blow the input line fuses on power up.
Product Line:
Altivar ATV66
Environment:
All
Cause:
Internal short inside the drive.
Resolution:
Before replacing the line fuses and power it back up again, please get a Fluke meter, and do a full diode static check on the input L1 L2 L3 and U, V, W output terminals to + and - bus.
The full diode check will show you two readings, you will measure .3vdc to .7vdc in forward bias direction or OL in the reverse direction.
Please reference the ATV66 troubleshooting and repair manuals VD0C06S701, and VD0C06S702 for more information on where and how do perform static checks on the drive.
DRIVES
Possible causes for an ATV66 drives to blow the input line fuses on power up.
Product Line:
Altivar ATV66
Environment:
All
Cause:
Internal short inside the drive.
Resolution:
Before replacing the line fuses and power it back up again, please get a Fluke meter, and do a full diode static check on the input L1 L2 L3 and U, V, W output terminals to + and - bus.
The full diode check will show you two readings, you will measure .3vdc to .7vdc in forward bias direction or OL in the reverse direction.
Please reference the ATV66 troubleshooting and repair manuals VD0C06S701, and VD0C06S702 for more information on where and how do perform static checks on the drive.
DRIVES
Publicado para: Schneider Electric Mexico


¿Necesitas ayuda?
Selector de productos
Encuentra rápida y fácilmente los productos y accesorios adecuados para tus aplicaciones.
Pedir presupuesto
Comienza tu consulta de ventas en línea y un experto se pondrá en contacto contigo.
¿Dónde comprar?
Encuentra fácilmente el distribuidor de Schneider Electric más cercano a ti.
Centro de ayuda
Encuentra recursos de soporte para todas tus necesidades en un solo lugar.