{}

Nuestras marcas

Impact-Company-Logo-English Black-01-177x54

Bienvenido(a) al sitio web para México de Schneider Electric

Te damos la bienvenida a nuestro sitio web para México.
Buscar Preguntas Frecuentes
With a SCADAPack 575 What Does the Message "This isn't a valid PLC Address, or PLC is busy, or media is off" mean?
When using a SCADAPack 575 and attempting to connect the logic debugger if the message "This isn't a valid PLC Address, or PLC is busy, or media is off" is displayed it can mean that the Logic Debugger service is not enabled in the rPAC.

To remedy this:
  1. Return to RemoteConnect
  2. Open the offline configuration
  3. In the "SCADAPack x70 Logic" section enable the "Logic Debugger Service"
  4. Download the configuration again.

Schneider Electric Mexico

Explora más
Rango:
Artículos que pueden ser útiles
Explora más
Rango: