Browse FAQs

How to setup the ATV61 drive for Apogee P1 card?

Published date: 25 June 2019

Issue:
How do you set up the ATV61 drive with an Apogee P1 card?

Product Line:
Altivar ATV61

Environment:
All

Cause:
Programming set up assistance.

Resolution:  
Menu 1.9
Address set to 0 to 99
Baud Rate:  4800, 9600, 19200, 38400, 57600, 76800
Network time out:  2 to 60 seconds
Please note you must power cycle after changing the address or Baud rate.