What is the kA rating of 29372 and 32623 Busbar Adapters for Compact NS/NSX<630 Circuit Breaker.

The breaking capacity (KA rating) of the system with the Busbar Adapters 29372 and 32623 connected with Compact NS/NSX<630 remains the as the Circuit Breaker connected. By adding the Busbar Adapters only the nominal current of Circuit Breaker is derated (see below table).

 
Derating Table
For NS 3PInBusbar Adaptor Reference
NS100100A29372
NS160160A29372
NS250250A29372
NS400400A32623
NS630570A32623