Issue
When the test and training set (TTS) is connected to the ADVC Controller it is showing a U-Series Recloser instead of a N-Series Recloser.
Product Line
ADVC II, Recloser, U-Series, N-Series, and W-Series
Environment
Testing the Recloser settings.
Cause
The old calibration files took the form of the first Recloser series that the TTS connects to. The series cannot be changed after that.
Resolution
In order to have the TTS have the ability to switch between series the calibration file needs to be N24-150s (24kV 150kV BIL 1A CT's).
Attached is the calibration file, instructions on how to check the calibration file and how to load the file, and application notes about the calibration file.
Note: The firmware of the ADVC Controller firmware must be A45-11.01 or above.
When the test and training set (TTS) is connected to the ADVC Controller it is showing a U-Series Recloser instead of a N-Series Recloser.
Product Line
ADVC II, Recloser, U-Series, N-Series, and W-Series
Environment
Testing the Recloser settings.
Cause
The old calibration files took the form of the first Recloser series that the TTS connects to. The series cannot be changed after that.
Resolution
In order to have the TTS have the ability to switch between series the calibration file needs to be N24-150s (24kV 150kV BIL 1A CT's).
Attached is the calibration file, instructions on how to check the calibration file and how to load the file, and application notes about the calibration file.
Note: The firmware of the ADVC Controller firmware must be A45-11.01 or above.
Released for: Schneider Electric Malaysia










Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.