Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

What is the replacement for NS630H with STR23SE trip unit?

The alternative replacement for NS630H with STR23SE trip unit is the new offer Compact NSX new Generation C63H32D630. C63H32D630 Circuit breaker, ComPacT NSX630H, 70kA/415VAC, 3 poles, MicroLogic 2.3...

Is M340 and M580 or Quantum can be installed in SIL1 application?

M340 is not and will not be certified SIL1. The only range with SIL certification is Quantum. It is certified up to SIL3. So the Quantum family (140cpu67160s, 140cpu65160s) could be used up to sil3...

What is the thickness of the Steel sheet metal used in Okken switchboard.

The Steel sheet metal thickness used in Okken switchboard is as listed below: Okken Steel sheet metal thickness Housing Thickness mm Door 2.00mm Rear panels 1.50mm Side panels 1.50mm Roof 1.50mm...

Is it possible to use 50Hz detuned reactor in a 60Hz system?

Detuned reactor works on both 50Hz/60Hz system based on the operation voltage required.

How to Disable the FTP and HTTP security in 140NOE77101 and 14077111...

These services can be disabled in Security Option available in Unity pro Ethernet communication configuration setting. Take a note these services can be disabled only on NOE firmware versions v6.0 or...

What is Concept 2.6SR1 error-870 while using CPU 40CPU53414B

Concept 2.6SR1 error -870 Goals and Symptoms: Using Concept 2.5SR2 and PLCs 140 CPU x34 1x (A) with EXEC Type E (e.g. Q58v117E.bin, Q5rv124E.bin etc.) the following error message may occur during...

Do Compact NSXm circuit breakers resist mechanical vibrations.

The Compact NSXm devices resist mechanical vibrations. They meet IEC 60068-2-6: -> 2.0 to 13.2 Hz and amplitude ±1 mm -> 13.2 to 100 Hz acceleration ±0.7 g.

What is the material composition of the Main Bus Bar of the Masterpact ACB?

The material composition used in the Main Bus Bar of the Masterpact Air Circuit breaker (ACB) is shown in the table attached. Note: AL/Sn5 means Aluminum connector with Sn5 coated

Popular Video FAQsPopular Videos

video-thumbnail
video-thumbnail
video-thumbnail
video-thumbnail
video-thumbnail
video-thumbnail
video-thumbnail
video-thumbnail
video-thumbnail

Learn more through our Generic Knowledge FAQsGeneral Knowledge

What is the selection criterion of Circuit Breakers for the Capacitor bank...

The selection should be done after derating the Circuit Breaker taking into consideration voltage variation and capacitors tolerances that could increase nominal current up to 1.5In. The Derating...