Characteristics
Main device application Motorrange Acti 9product name Acti 9 iC60product or component type Miniature circuit-breakerdevice short name IC60Lpoles description 2Pnumber of protected poles 2[In] rated current 10 Anetwork type ACtrip unit technology Magneticcurve code MAbreaking capacity 15 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-220 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-240 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2utilisation category Category A conforming to EN 60947-2Category A conforming to IEC 60947-2suitability for isolation Yes conforming to EN 60947-2Yes conforming to IEC 60947-2standards EN 60947-2IEC 60947-2Complementary network frequency 50/60 Hzmagnetic tripping limit 12 x In +/- 20 %[Ics] rated service breaking capacity 10 kA 50 % conforming to EN 60947-2 - 380...415 V AC 50/60 Hz7.5 kA 50 % conforming to EN 60947-2 - 440 V AC 50/60 Hz10 kA 50 % conforming to IEC 60947-2 - 380...415 V AC 50/60 Hz7.5 kA 50 % conforming to IEC 60947-2 - 440 V AC 50/60 Hz20 kA 50 % conforming to EN 60947-2 - 220...240 V AC 50/60 Hz20 kA 50 % conforming to IEC 60947-2 - 220...240 V AC 50/60 Hzlimitation class 3 conforming to EN 60898-13 conforming to IEC 60898-1[Ui] rated insulation voltage 500 V AC 50/60 Hz conforming to EN 60947-2500 V AC 50/60 Hz conforming to IEC 60947-2[Uimp] rated impulse withstand voltage 6 kV conforming to EN 60947-26 kV conforming to IEC 60947-2contact position indicator Yes