{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
Why does the load side of the shorting contactor connect to A2, B2 and C2 on the ATS48 soft start?

Article available in these languages: Spanish

Issue:
Shorting contactor wiring

Product Line:
ATS48

Environment:
All models and serial numbers

Cause:
None

Resolution:
The A2, B2 and C2 terminals on the soft start provide a current path through internal current transformers.  This provides overload protection when the shorting contactor is activated.
Refer to page 81 in the ATS48 Installation Guide for a wiring diagram.

Schneider Electric Nigeria

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: