Missing links to raw status information on Symmetra UPS
Issue
Links to access the raw status data of Symmetra intelligence modules are missing in the Network Management Card (NMC) interface

Product Line
  • Network Management Card 2 - AP9630/AP9630CH, AP9631/AP9631CH, AP9635/35CH
  • Symmetra UPS systems

Environment
  • Firmware version AOS 6.4
  • All serial numbers

Resolution
Links to access the raw status information of the Symmetra intelligence modules are missing from AOS 6.4. This will be resolved in a future release, and this KB article will be updated when a fixed version is available. It is possible to access the raw status information of the intelligence modules by modifying the URL as shown in the steps :

 

Step 1 - Navigate to the IM information page (Status --> UPS --> Intelligence modules)


Step 2 - Select "View All Battery Raw Status Data" at the bottom of the page


 

Step 3 - Modify the end of the URL from "uprawbatt.htm" to "upraw.htm", and press enter to reload the page




This page will show all raw status information for the Intelligence Modules, Power Modules and any connected Battery Frames



 

Schneider Electric Nigeria

Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.