Why did my Magelis lose tag communications after building changes on my CPU?

Issue
After a build change using Unity Pro or Control Expert the tags on the HMI indicated communication errors.

Product line
Control Expert

Resolution
This typically means that the Magelis project was created in Vijeo Designer using linked variables. To correct this issue open the Vijeo Designer project and from the Navigator right click on variables and update the link with the new CPU project file generated after the most recent changes. Once this is updated, build and transfer the Vijeo Designer project to the Magelis.