Where is an S-Flex run contact wired?

Issue:

On which terminals are a run contact landed on the S-Flex?

 

Product Line:

S-Flex

 

Environment:

Design series E for models with bypass

All models without bypass

 

Cause:

Hardwiring a run contact

 

Resolution:

The S-Flex models without bypass use a dry run contact wired between terminals P24 and F. This is a 24Vdc circuit.

The S-Flex models with bypass use a dry run contact wired between terminal 5 and 6. This is a 120Vac circuit and controls Start/Stop when the HOA selector is in the AUTO position.