Welcome to the Schneider Electric Website

Welcome to our website.

Select your location

Welcome the the Schneider Electric French website. It looks like you are located in the United States, would you like to change your location?

Traduisez en francais
View all   Marine
G55TUPU60HXS Picture of product Schneider Electric

G55TUPU60HXS

Product Logo
G55TUPU60HXS Picture of product Schneider Electric
G55TUPU60HXS
Product Logo

MGE Galaxy 5500 60kVA 400-415V Single UPS Off Shore IP22 RAL 7035, Start-up 5X8

Show more characteristics
The maximum number of products that can be compared is 4. Remove already added products.

  • Overview
    Presentation
    UPS is designed to meet the offshore standard requirement.
    Lead time
    Special Order - Call for Quoted Lead Times
    General
    provided equipment
    Installation guide
    User manual
    bypass wiring configuration
    4 wire (3P + N)
    5 wire (3P + N + E)
    bypass voltage tolerance
    +/- 10 % settable from +/- 4/6/8 and 10 %
    max bypass input current
    87 A
    bypass current protection
    125 A
    Number of power module free slots
    0
    Number of power module filled slots
    0
    redundant
    No
    UPS size
    WS
    Physical
    depth
    85.5 cm
    height
    218 cm
    mounting preference
    No preference
    net weight
    456 kg
    mounting mode
    Not rack-mountable
    two post mountable
    0
    USB compatible
    No
    width
    71.2 cm
    Input
    network frequency
    45...65 Hz
    number of input connectors
    1 hard wire 4-wire (3P + E)
    1 hard wire 4-wire (3P + N)
    input voltage limits
    323...437 V 380 V
    340...460 V 400 V
    353...477 V 415 V
    inputvolt_other
    380 V
    415 V
    maximum input current
    115 A
    switching current capacity
    125 A
    max short time withstand current
    20 kA
    input harmonic distortion
    Less than 5 % for full load
    input protection type
    GL fuse
    input voltage
    400 V 3 phases
    load power factor
    0.9
    cos phi
    1
    Output
    rated power in W
    54000 W
    Maximum configurable power in W
    54000 W
    harmonic distortion
    Less than 2 %
    output frequency
    50 Hz programmable +/- 0.5 / 1 / 2 / 4 / 6 / 8 % sync to mains
    50 Hz +/- 0.1 % for 50 Hz nominal unsynchronised
    outputvolt_other
    380 V
    415 V
    crest factor
    3 : 1
    UPS type
    Double conversion online
    Wave type
    Sine wave
    output voltage tolerance
    +/- 2% static and 100% load step
    output harmonic distortion
    < 1% linear load and < 2.5% non-linear load
    output overload operation
    10 minutes at 125% and 60 seconds at 150%
    required output current protection
    87 A
    neutral output current
    87 A
    bypass type
    Built-in maintenance bypass
    Built-in static bypass
    Optional external bypass
    curve equation
    Efficiency