Issue:
On-OFF control for PID function block in Unity Pro/EcoStruxure Control Expert
Product Line:
Unity Pro, EcoStruxure Control Expert
Resolution:
No. The PID blocks in Unity Pro does not have a setting for ON - OFF control. For ON-OFF control, the output of the PID block can be connected to the input of a PWM function block.