Behavior of the logical outputs if they are written in different tasks.

Goals and Symptoms

Behavior of the logical outputs if they are written in different tasks.

Causes and Fixes

If local logical outputs are written in different tasks of the LMC (Auxiliary task, Motion task or event task) inconsistencies between the programmed value and the physical value of the output can occur.
- This behavior appears if the same output is written in different tasks but also if 2 different outputs are written in different tasks.
- This behavior is common to all the platforms running with Codesys and is not regarded as misbehavior.
- It cannot be modified
- Solution: use LMC_ExplicitOutput FB if you need to write logical outputs from different tasks of the LMC.

Attachments

(Removed File URL: 198428_B832/Behaviour_of_the_logical_outputs_V1_.zip)(Removed Image URL: /PubResEXPORT.nsf/2b87ee90be777fc085257c28006ee4ef/ef76aab6e13c647cc12575ad005297d5/fl_block_5/0.64E?OpenElement&FieldElemFormat=gif)


Legacy KB System (APS) Data: RESL198428 V1.0, Originally authored by MaPr on 05/05/2009, Last Edited by MaPr on 05/05/2009
Related ranges: Lexium Controller

Schneider Electric Netherlands

bijlage(n)
Behaviour_of_the_logical_outputs_V1_.zip [73.67 KB]
Ontdek meer
Productfamilie
Ontdek meer
Productfamilie
  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Offerte aanvragen?
  • Openingstijden & adressen
  • Vind distributeur
  • Schneider Electric-community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Dataprivacy
  • Cookiekennisgeving
  • Juridische informatie
  • Change your cookie settings