Com'X system has been configured with fast logging (less than 15 min logging interval ) with many topics on many devices, the device is very slow, why?

The device performance has degraded, to many data to manage in time, all monitoring data are needed ?
We recommend  to reduce the  logging interval frequency (> or = 15min.) or reduce the amount of data being logged.
In the future the Com’X will come with a tool to help assess optimum configuration.