Waarmee kunnen wij u vandaag helpen?

Why is ENM8.3 not filtering low priority tags from PME8 system

Issue

Why is ENM8.3 not filtering low priority tags from PME8 system

Product Line
Power Monitoring Expert 8.x
ENM v8.3

Environment
ENM Configuration

Cause
Alarm Configurator in PME is used to build various alarm rules by assigning priorities 100 and higher. ENM configuration of the PME alarms are working as expected; however, meter events from PME with priorities as low as 10 are being sent out to the subscriptions recipients.

Resolution
In ENM Configuration, select Subscriptions Recipients and confirm which Tag Filter is selected. ENM by defaul,t has all low priority and high priority events from PME. If the Tag Filter "All" is selected in the subscription, then all events will be sent out to the subscription's recipients.


ENM Subscription 1

ENM Subscription 2



ENM Subscription 3

For each subscription recipient, build the subscription by using the Add Subscription for each Tag filter in the system, except the tag filter "All"

NOTE: Starting in PME2020, the ENM function has been embedded within the PME web application https://www.se.com/us/en/faqs/FA403988/

Schneider Electric Netherlands

Ontdek meer
Product:
Ontdek meer
Product:
  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Offerte aanvragen?
  • Openingstijden & adressen
  • Vind distributeur
  • Schneider Electric-community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Dataprivacy
  • Cookiekennisgeving
  • Juridische informatie
  • Change your cookie settings