The nominal voltage for the 33664 MN device is 380/480 Vac, what are the voltage limits ?

  • What the actual minimum "hold" value is. Is it 70% of 480, or 70% of 380? It cannot be both, since it is the same device.

The minimal "hold" value is 70% of 380V

Tripping value is 35% of 480V

This practically means the coil operates between 168V (Drop-off value = Breaker Trip Mechanism Activated, breaker opens contacts) and 266V (Pick-up value = Breaker Trip Mechanism unlocked, breaker can be closed again)