{}

Onze merken

Impact-Company-Logo-English Black-01-177x54

Welkom op de website van Schneider Electric

Welkom op onze website.
Veelgestelde vragen (FAQ's) zoeken
How to change query name (measure name) in dashboard?
Issue
How to change query name (measure name) in dashboard

Product Line
Power Monitoring Expert 8.0

Envrionment
SQL Server management Studio

Resolution
*Warning: Irreparable database damage can occur. This procedure should only be performed by users familiar with SQL Server Management Studio. Databases should be backed up prior to performing this procedure.*

Here are the steps you can change the measurement name on Dashboard to what you want to display (take Block Demand Apparent Power Total as example)
1.  Open SQL Management Studio and connect ot the PME instance
2.  Find ResourceKeyId in Internationalization.LocalizedString in ApplicationModules database, such as
SELECT *  FROM [ApplicationModules].[Internationalization].[LocalizedString]  where value = 'block demand apparent power total'
3.  Change the Value from "Block Demand Apparent Power Total" to "kVA Total"
4.  Refresh Web Application and you will see the new measurement name.

Screen capture can be found in attachment (Screen Capture).

Schneider Electric Netherlands

bijlage(n)
Screen_Capture.png [24.56 KB]
Ontdek meer
Productfamilie
Mogelijk nuttige artikelen
Ontdek meer
Productfamilie