Waarmee kunnen wij u vandaag helpen?

ENM Monitoring and Diagnostics pages display "[Invalid Date]" for timestamps

Issue

The Event Notification Module (ENM) Monitoring and Diagnostics pages display [Invalid Date] in timestamp columns instead of the actual timestamp.

Product Line

ENM 8.3.x

Environment

PowerSCADA Expert 8.1

Power Monitoring Expert 8.1

Cause

Some Windows locales use special characters for AM/PM notation (e.g., Italian [Switzerland], Chinese [Singapore]). When Windows is configured to use one of these locales, ENM cannot properly format timestamps, resulting in [Invalid Date].

Resolution

Change the Windows locale to one that uses standard AM/PM characters.
Examples:

  • Italian (Italy)
  • Chinese (China)

Steps:

  1. Open Control Panel → Region and Language.
  2. Change the locale to a supported setting.
  3. Restart ENM services if necessary.

Notes

  • This issue applies only to ENM 8.x and PME 8.1.
  • Newer versions of PME and ENM have resolved this locale parsing issue.

Recommendation

If you are using an older version of PME, consider upgrading to the latest version for improved protocol support and security. For assistance with integration or upgrades, contact Schneider Electric Technical Support at: pmo.support@se.comPME Version History

Schneider Electric Netherlands

Ontdek meer
Productfamilie
Ontdek meer
Productfamilie
  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Offerte aanvragen?
  • Openingstijden & adressen
  • Vind distributeur
  • Schneider Electric-community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Dataprivacy
  • Cookiekennisgeving
  • Juridische informatie
  • Change your cookie settings