Is it possible to use Ethernet IP and Ethernet TCP on the same network using an ATV630?
Issue:
Usage of Ethernet IP option and the integrated Ethernet TCP on the same network with an ATV630
Product Line:
Altivar 630
Environment:
All serial numbers
Cause:
I have several ATV630 monitoring Ethernet, some have option Ethernet cards and some do not.
Resolution
Ethernet IP and Ethernet TCP cannot be used on the same network.
Usage of Ethernet IP option and the integrated Ethernet TCP on the same network with an ATV630
Product Line:
Altivar 630
Environment:
All serial numbers
Cause:
I have several ATV630 monitoring Ethernet, some have option Ethernet cards and some do not.
Resolution
Ethernet IP and Ethernet TCP cannot be used on the same network.