Galaxy RPP “Fingersafe IP2X” NQ Panelboards

Issue:
The new Galaxy RPP has multiple panelboard options.  One of them is the IP2X Fingersafe panelboard which greatly restricts exposure to live parts.

These panelboards use the standard Square D QOB breakers but require some adapters to make them fit and increase safety.

Product line:
GRPPIP2X84, GRPPIP2X89

Environment:
All models, all serial numbers

Cause:
Electrocution is one of the top causes of construction injury.  The NQ panelboard reduces this risk by limiting exposure to live components.

Resolution:
To install standard Sq D QOB breakers into the Galaxy RPP with the NQ Panelboard, you will need an accessory jaw kit, and Fingersafe Barriers.

Parts:

Catalog NumberQuantity per packageDescription
QOFSBF1212NQ IP2X Bus Finger Filler *3
QOFSLALB1212NQ IP2X QO(B) Lug Cover Low Amp
QOFSHALB1212NQ IP2X QO(B) Lug Cover High Amp
QO1PJ1515QOB Jaw Kit4
QOBRT1QOB Breaker Removal Kit *4
*3 Used only with Standard IP2X design
*4 Used only with Enhanced IP2X design


References:
https://www.apc.com/shop/us/en/products/Galaxy-RPP-with-fingersafe-IP2X-panelboard-white/P-GRPPIP2X84

https://download.schneider-electric.com/files?p_File_Name=998-20824083_GMA-US_Galaxy+RPP+brochure_HR_WEB.pdf&p_Doc_Ref=GalaxyRPP_Brochure_EN&p_enDocType=Catalog

https://download.schneider-electric.com/files?p_enDocType=Brochure&p_File_Name=1640BR1701_NQ_FingerSafe1-2019.pdf&p_Doc_Ref=1640BR1701

Schneider Electric Netherlands

bijlage(n)
998-20824083_GMA-US_Galaxy RPP brochure_HR_WEB.pdf [3.82 MB]
1640BR1701_NQ_FingerSafe1-2019.pdf [1.09 MB]
Ontdek meer
Product:
Productfamilie
Ontdek meer
Product:
Productfamilie
  • Productdocumentatie
  • Software & firmware
  • Productselector
  • Productvervanging
  • Help- en Contact Center
  • Offerte aanvragen?
  • Openingstijden & adressen
  • Vind distributeur
  • Schneider Electric-community
  • Werken bij
  • Bedrijfsprofiel
  • Wangedrag melden
  • Toegankelijkheid
  • Newsroom
  • Investeerders
  • EcoStruxure
  • Vacature zoeken
  • Blog
  • Als eerste op de hoogte nieuws?
  • Dataprivacy
  • Cookiekennisgeving
  • Juridische informatie
  • Change your cookie settings