A user sees the following error ("Configuration error, The source is improperly configured or the requested register does not exist") in Vista when linking to an ASCII string register that is set up for a custom device in Modbus Device Importer (MDI).
Product Line:
ION Enterprise 5.6.x
ION Enterprise 6.0.x
StruxureWare Power Monitoring 7.0.x
Power Monitoring Expert 7.2.x
Power Monitoring Expert 8.x
Environment:
Vista
Modbus Device Importer
Cause:
When an ASCII register is set up in the Modbus Device Importer, the register is not associated with the appropriate register type in the translator files.
Resolution:
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop)".
- A user will need to manually modify the ION translator file for the device driver to assign the register to the appropriate format
- A user is only able to select the ASCII register format for a register added to an "External Numeric Manager"
4. In the .xml file locate the ASCII register and make note of the ION handle number. In the example below the handle number is 135266305
Publisert for: Schneider Electric Norway


Trenger du hjelp?
Start her!
Finn svar nå. Søk etter en løsning på egen hånd, eller kontakt en av våre eksperter.
Kontakt kundestøtten
Ta kontakt med kundeteamet vårt for mer informasjon, teknisk støtte, hjelp med klager og mer.
Hvor kan du handle?
Finn din nærmeste Schneider Electric-distributør enkelt.
Bla gjennom ofte stilte spørsmål (FAQ)
Få svarene du trenger ved å se etter emnerelaterte ofte stilte spørsmål (FAQ).
Kontakt salgsavdelingen
Start salgsforespørselen på Internett, så blir du kontaktet av en ekspert.