EcoStruxure Control Expert V14.0 can stop working by doing a right click on a LD or LL984 contact
1. Issue
EcoStruxure Control Expert V14.0 stops working by doing a copy, paste, or cut of a graphic element from another software (e.g. Vijeo Designer, Word), then using right click in a LD or LL984 editor on one of the following selections:
For LD: Link (vertical, horizontal), Derivation, Contact, Coil, Compare, Operate, Input and output pins of function blocks (CTU, ...)
For LL984: Link (vertical, horizontal), Contact, Coil, Values inside function blocks
2. Product Line
EcoStruxure Control Expert V14.0
3. Resolution
One possible workaround is to perform CTRL+C command in EcoStruxure Control Expert V14.0 software. By doing this we will avoid the shutdown of EcoStruxure Control Expert, if we do a right click on LD or LL984 editor.
The correction is brought in EcoStruxure Control Expert V14.0 with the installation of ControlExpert_V140_HF0544798R hot fix.
This unexpected behaviour is resolved in EcoStruxure Control Expert V14.1.
One possible workaround is to perform CTRL+C command in EcoStruxure Control Expert V14.0 software. By doing this we will avoid the shutdown of EcoStruxure Control Expert, if we do a right click on LD or LL984 editor.
The correction is brought in EcoStruxure Control Expert V14.0 with the installation of ControlExpert_V140_HF0544798R hot fix.
This unexpected behaviour is resolved in EcoStruxure Control Expert V14.1.
Publisert for: Schneider Electric Norway


Trenger du hjelp?
Produktvelger
Velg riktige produkt og kompatibelt tilbehør raskt og enkelt.
Be om tilbud
Start din salgsforespørsel online, og vi vil kontakte deg.
Hvor kan du handle?
Finn din nærmeste Schneider Electric-distributør enkelt.
Hjelpesenter
Finn alle nødvendige supportressurser samlet på ett sted.