Can the OA1 output of Tesys U be used with multifunction unit to drive a separate motor contactor.

Output OA1 for Tesys U with base contactor (LUB**) is only used to drive the contactor embedded inside the TesysU contactor base LUB.
 
In order to use multifunction control unit and drive a separate contactor then use LUTM controller base for this application.