To enable or disable these features it's important to follow the instructions carefully for a consistant result, by doing the process too quickly or slowly may not change the state correctly.
For either option: Press and Hold toggle button 1 for greater than .5 seconds, quick press either button 3 or 4 * important that it's a quick press <0.5 sec, then release button 1 again after about 0.5-1 second, if you press and hold buttons 3 or 4 for too long or release button 1 and 3 or 1 and 4 at the same time the unit will not change state.
9 Switching of the inbuilt C-Bus power supply and C-Bus system clock if required
Ensure adequate C-Bus power supply is enabled in the bus by referring to the indication on the unit and the bus design by checking the right amount of power supplies enabled. In case of low C-Bus bus power indication, switch the inbuilt C-Bus Power supply in the dimmer.
Note: If the inbuilt switchable C-Bus power supply is enabled, the dimmer supplies power upto 200 mA to the network when connected to the mains.
How to enable/disable C-Bus power supply
The integrated C-Bus Power Supply can be enabled or disabled via the front panel by performing a short press on the top right channel button whilst holding down the top left channel button to toggle the enabled state, refer 9(a)
The enabled status of the integrated C-Bus Power Supply is shown on the Unit Indicator. Refer to diagnosis section (b).
The C-Bus Indicator state shows the state of the network voltage. If the C-Bus Indicator is flashing or off, the network voltage is too low, meaning there is insufficient C-Bus Power. additional power supplies may need to be enabled.
NOTE: It is important to ensure that no more than 2A of total C-Bus Power Supply capacity is enabled/connected to any one C-Bus network.
How to enable/disable the C-Bus system clock generator (if required)
The system clock is used to synchronize data communication over a C-Bus network. If a system clock is required, it can be enabled from the SpaceLogic C-Bus Commission software and the indicator buttons on the dimmer.
The integrated C-Bus Clock generator can be enabled or disabled via the front panel by performing a short press on the top second-to-right button whilst holding down the top left channel button to toggle the enabled state, refer 9(b)
For either option: Press and Hold toggle button 1 for greater than .5 seconds, quick press either button 3 or 4 * important that it's a quick press <0.5 sec, then release button 1 again after about 0.5-1 second, if you press and hold buttons 3 or 4 for too long or release button 1 and 3 or 1 and 4 at the same time the unit will not change state.
9 Switching of the inbuilt C-Bus power supply and C-Bus system clock if required
Ensure adequate C-Bus power supply is enabled in the bus by referring to the indication on the unit and the bus design by checking the right amount of power supplies enabled. In case of low C-Bus bus power indication, switch the inbuilt C-Bus Power supply in the dimmer.
Note: If the inbuilt switchable C-Bus power supply is enabled, the dimmer supplies power upto 200 mA to the network when connected to the mains.
How to enable/disable C-Bus power supply
The integrated C-Bus Power Supply can be enabled or disabled via the front panel by performing a short press on the top right channel button whilst holding down the top left channel button to toggle the enabled state, refer 9(a)
The enabled status of the integrated C-Bus Power Supply is shown on the Unit Indicator. Refer to diagnosis section (b).
The C-Bus Indicator state shows the state of the network voltage. If the C-Bus Indicator is flashing or off, the network voltage is too low, meaning there is insufficient C-Bus Power. additional power supplies may need to be enabled.
NOTE: It is important to ensure that no more than 2A of total C-Bus Power Supply capacity is enabled/connected to any one C-Bus network.
How to enable/disable the C-Bus system clock generator (if required)
The system clock is used to synchronize data communication over a C-Bus network. If a system clock is required, it can be enabled from the SpaceLogic C-Bus Commission software and the indicator buttons on the dimmer.
The integrated C-Bus Clock generator can be enabled or disabled via the front panel by performing a short press on the top second-to-right button whilst holding down the top left channel button to toggle the enabled state, refer 9(b)
Released for:Schneider Electric New Zealand