APC Network Management Card (NMC) has no LED indicators or shows no power

Issue:
APC Network Management Card(s) installed in a compatible UPS, but neither the Link nor Status LEDs are illuminated.

Product Line:

  • Network Management Card 1 (NMC1) - AP9617, AP9618, AP9619
  • Network Management Card 2 (NMC2) - AP9630/AP9630CH, AP9631/AP9631CH, AP9635/AP9635CH
  • Network Management Card 3 (NMC3) - AP9640, AP9641, AP9643

Environment:
All Serial Numbers
All Firmware Revisions

Cause:
The NMC may not be receiving power due to several potential issues, including:

  • Loose connections or improper seating of the NMC.
  • A fault in the NMC hardware.
  • Firmware issues or corrupt settings.

Resolution:
1. Check UPS Status- Ensure the UPS is turned on and functioning properly. If the UPS is off, turn it on and check if the NMC powers up.

2. Inspect Connections -Remove the NMC and check for any visible damage. Ensure that it is properly seated in the SmartSlot of the UPS and it is secured with the provided screws.

3. Try a Different SmartSlot -If your UPS has multiple SmartSlots or if you have another UPS with SmartSlot for management cards, try inserting the NMC into a different SmartSlot to rule out a faulty connection. If the NMC functions properly in another UPS, you might want to upgrade your UPS's firmware by following the instructions provided in Schneider Electric KBase FA164737.

4. Try a Different NMC - If another known good NMC is available, swap the one in question by inserting it into the same SmartSlot in the UPS to help isolate the issue.

5. Format the Card (NMC2/NMC3 only) - Use a paperclip and press and hold the NMC's pinhole reset button for around 20 seconds. This will erase all user settings and configuration, including TCP/IP network settings.

6. Attempt to Update the NMC Firmware via XMODEM (NMC2/NMC3 only) - For step-by-step instructions on updating the NMC firmware through Terminal Emulation XMODEM, refer to Schneider Electric KBase FA156047.

Schneider Electric Philippines

APC Network Management Card (NMC) has no LED indicators or shows no power

Issue:
APC Network Management Card(s) installed in a compatible UPS, but neither the Link nor Status LEDs are illuminated.

Product Line:

  • Network Management Card 1 (NMC1) - AP9617, AP9618, AP9619
  • Network Management Card 2 (NMC2) - AP9630/AP9630CH, AP9631/AP9631CH, AP9635/AP9635CH
  • Network Management Card 3 (NMC3) - AP9640, AP9641, AP9643

Environment:
All Serial Numbers
All Firmware Revisions

Cause:
The NMC may not be receiving power due to several potential issues, including:

  • Loose connections or improper seating of the NMC.
  • A fault in the NMC hardware.
  • Firmware issues or corrupt settings.

Resolution:
1. Check UPS Status - Ensure the UPS is turned on and functioning properly. If the UPS is off, turn it on and check if the NMC powers up.

2. Inspect Connections - Remove the NMC and check for any visible damage. Ensure that it is properly seated in the SmartSlot of the UPS and it is secured with the provided screws.

3. Try a Different SmartSlot - If your UPS has multiple SmartSlots or if you have another UPS with SmartSlot for management cards, try inserting the NMC into a different SmartSlot to rule out a faulty connection. If the NMC functions properly in another UPS, you might want to upgrade your UPS's firmware by following the instructions provided in Schneider Electric KBase FA164737.

4. Try a Different NMC - If another known good NMC is available, swap the one in question by inserting it into the same SmartSlot in the UPS to help isolate the issue.

5. Format the Card (NMC2/NMC3 only) - Use a paperclip and press and hold the NMC's pinhole reset button for around 20 seconds. This will erase all user settings and configuration, including TCP/IP network settings.

6. Attempt to Update the NMC Firmware via XMODEM (NMC2/NMC3 only) - For step-by-step instructions on updating the NMC firmware through Terminal Emulation XMODEM, refer to Schneider Electric KBase FA156047.

Schneider Electric Philippines

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:

Need help?

  • Start here!

    Find answers now. Search for a solution on your own, or connect with one of our experts.

  • Contact Support

    Reach out to our customer care team to receive more information, technical support, assistance with complaints and more.

  • Where to buy?

    Easily find the nearest Schneider Electric distributor in your location.

  • Search FAQs

    Search topic-related frequently asked questions to find answers you need.

  • Contact Sales

    Start your sales inquiry online and an expert will connect with you.

I'd like to receive news and commercial info from Schneider Electric and its affiliates via electronic communication means such as email, and I agree to the collection of information on the opening and clicks on these emails (using invisible pixels in the images), to measure performance of our communications and improve them. For more details, please read our Privacy Policy.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and Contact Center
  • Find our Offices
  • Get a Quote
  • Where to buy
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.