MV-90: Meter Events

Issue:

How to retrieve meter events in MV‑90 and decode the events that MV‑90 reports.

Product Line:

MV‑90

Environment:

Meter Events

TIM: Translation/Interface Module

Cause:

Event codes/Descriptions can differ between what the meter records and what MV‑90 shows, and not all events may be retrieved directly. Conversion/mapping depends on the TIM.

Resolution:

About event retrieval

  • The TIM automatically reads the meter Event Log for the same time period as an All/Partial Read.

To retrieve events:

  1. Perform an All/Partial Read.
  2. Go to Meter Events → Event Maintenance → choose the RecorderID.
  3. Change the Start Date to an earlier date → Go.

About decoding MV‑90 event codes:

  • Refer to the latest TIM_Appnote in:
    C:\MV90xi\TIMs (contains conversion of ION events to MV‑90 events).