How many Hart variables can be on Advantys Island?

Issue:
What is the maximum number of Hart variables can be used on an Advantys Island

Product line:
Advantys

Environment:
Advantys configuration software

Cause:
Using Hart devices on an Advantys Island.

Resolution:
The Advantys Island with Hart allows the following;
4 Hart Variables per channel
32 channels per Island
128 Variables per Island.