{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
Search FAQs
How to measure the Contact Resistance for (NS1600N 3P ,NSX400N , NSX100F ) ? How many additional " OF "Auxiliary contacts can be installed on NW Air circuit breaker ?
"Attached (Contact Resistance on Compact NS_NSX MCCBs.pdf), you will find the new procedures for measuring the contact resistance. The procedure can be summarized as follows:


Pole resistance measurement:
1. Manually operate 5 times the circuit breaker to the OFF and then to the ON position (without current)
2. Apply test current across one pole for at least 30mins
3. Record the millivolt drop and calculate the resistance (R = U / I)
4. Take 3 consecutive measurements operating each time the device and calculate the average
5. Repeat for each pole

Concerning the acceptable value, values less than or equal to 1.3 times the reference value are acceptable in view of measurement u
ncertainties."

Schneider Electric Saudi Arabia

Attachment(s)
Contact Resistance on Compact NS_NSX MCCBs.pdf [213.38 KB]
Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: