{}

Sök bland vanliga frågor (FAQ)

{"searchBar":{"inputPlaceholder":"Sök med nyckelord eller ställ en fråga","searchBtn":"Sök","error":"Ange ett sökord"}}

Do the M580 Ethernet ports have to be on the same subnet.

Issue:
Can the M580  built-in CPU Ethernet ports be setup to be on two different Ethernet subnetworks?

Product Line:
M580

Resolution:
The M580  built-in CPU Ethernet ports can not be setup to be on two different Ethernet subnetworks. The M580 Service port (Main IP Address) and the (IP Address A) Device network ports (Port2 and Port3) have to be assigned IP addresses that are on the same subnetwork. To have a separate and different Ethernet network, you must use a BMENOC0301 module in the M580 main rack.

Schneider Electric Sverige

Var det här till hjälp?

Utforska mer
Utforska mer