Issue:
InRow Entering Fluid Temp threshold is not alarming
Product line:
InRow
Environment:
Data Center Cooling
Cause:
Resolution:
In the newest firmware ACRC 372 and higher the entering fluid temp alarm threshold violation will not be reported unless two conditions are met. The unit has a >=40% valve position opening, and the entering temperature is above the threshold.
InRow Entering Fluid Temp threshold is not alarming
Product line:
InRow
Environment:
Data Center Cooling
Cause:
Resolution:
In the newest firmware ACRC 372 and higher the entering fluid temp alarm threshold violation will not be reported unless two conditions are met. The unit has a >=40% valve position opening, and the entering temperature is above the threshold.
Released for: Schneider Electric Singapore
Issue:
InRow Entering Fluid Temp threshold is not alarming
Product line:
InRow
Environment:
Data Center Cooling
Cause:
Resolution:
In the newest firmware ACRC 372 and higher the entering fluid temp alarm threshold violation will not be reported unless two conditions are met. The unit has a >=40% valve position opening, and the entering temperature is above the threshold.
InRow Entering Fluid Temp threshold is not alarming
Product line:
InRow
Environment:
Data Center Cooling
Cause:
Resolution:
In the newest firmware ACRC 372 and higher the entering fluid temp alarm threshold violation will not be reported unless two conditions are met. The unit has a >=40% valve position opening, and the entering temperature is above the threshold.
Released for: Schneider Electric Singapore












Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales enquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.