Why won't my M580 or M340 PLC will not go into run? I have a BMXXBE1000 installed in the rack.

Title
Run issues with improper BMXXBE1000 installation
 
Issue
BMXXBE1000 installation
 
Product Line
M580, M340
 
Environment
Unity Pro, Control Expert
 
Resolution
If the BMXXBE1000 is causing this issue it will be caused by either improper addressing of the racks, or the Cable/Terminators are loose/missing.
-Please ensure that the terminators are securely fastened to the units.
-Please ensure that the cable is connected (to both sides) and snug.
-Please ensure that you have unique addresses for each rack involved in the setup.