How to configure RemoteConnect x70 Device as Modbus RTU Slave?

Published date: 04 December 2019

When the SCADAPack x70 device is operating as a Modbus RTU Slave, it can communicate with up to 4 Modbus RTU Masters, 1 through each serial port on the device.

Supported Data Types
When the SCADAPack x70 device is operating as a Modbus RTU Slave, it supports the IEC 61131-3 data types described below.
SCADAPack Object Type Modbus IEC Type Function Code Modbus Operation
DIGITAL DISCRETE 1 Read Coils
2 Read Status Registers
5 Write Coil
15 Write Multiple Coils
ANALOG UINT 3 Read Holding registers
4 Read Input registers
6 Preset Single Register
16 Preset Multiple Registers
DINT 3 Read Holding register pairs
4 Read Input register pairs
16 Preset Multiple Register pairs
INT 3 Read Holding registers
4 Read Input registers
6 Preset Single Register
16 Preset Multiple Registers
REAL 3 Read Holding register pairs
4 Read Input register pairs
16 Preset Multiple Register pairs
DISCRETE 1 Real Coils (up to 16)
2 Read Input Status (up to 16)
15 Write Multiple Coils (up to 16)
COUNTER UINT 3 Read Holding registers
4 Read Input registers
6 Preset Single Register
16 Preset Multiple Registers
UDINT 3 Read Holding register pairs
4 Read Input register pairs
16 Preset Multiple Register pairs

To configure RemoteConnect Project as Modbus RTU Slave:
 1. Verify that Modbus RTU Slave checkbox is checked from Project Configuration Options



2. Go to Configuration Modbus >Slave/Server to Select Modbus Slave Addressing Mode
at least one of the serial ports needs to be configured for Modbus 


 
  • Port Function Should be ‘Modbus’
  • Port Mode, Baud rate and the Parity should be configured as the Modbus Master
  • Modbus RTU Slave >Station Address should be unique per Modbus Link between 1 to 247
3. Go to Configuration Modbus >Slave/Server to Select Modbus Slave Addressing Mode



SCADAPack x70 devices support 5-digit and 6-digit Modbus addressing, you can set up a Modbus Slave to have any of these registers available to a Modbus Master that requests them.

The table below maps 5-digit Modbus address ranges to the equivalent 6-digit Modbus address range.
Use this information to stay within the appropriate address range when moving from 5-digit to 6-digit Modbus addressing.
Type 5-Digit Modbus Address Range Equivalent 6-Digit Modbus Address Range
Coil 1 to 9999 1 to 9999
Status register 10001 to 19999 100001 to 109999
Input register 30001 to 39999 300001 to 309999
Holding register 40001 to 49999 400001 to 409999

4.  To assign a Modbus address to an Objects, Open Objects >Object Configuration
      Select and object and from Modbus tab insert the proper Modbus address and type


5. Apply and save the project




 
 





 

 