SBO upgrade process failed (SBO 1.8.x to SBO 1.9.x)
Upgrade failed when upgrading Automation Server from SBO version 1.8.x to 1.9.x

Log indicate:
(Device Administrator | View | Last Upgrade Log)
ERROR:        Exception encountered during database upgrade : StartUpMode UpgradeDatabase : RecoverableException: d:\dev\rb-rb-1.9.2-system\source\server\nsp_servers\csc\LonTypes\source\Lon2MapFileUtil.cpp(185) Invalid Data Error: Invalid_Data (0x10000) in module Impex(57). "Map data is too old for type: public.lon2.devicetemplates.pid90003A8200E90401. You need to run the Lon Repair command in the latest version of workstation"
2019-04-10 07:14:02  INFORMATION:  Database upgrade time: 5.28889 seconds
2019-04-10 07:14:02  INFORMATION:  =============  End Configuration Database Upgrade  =============
Source version: 1.8.1.79 Target Version: 1.9.2.45

Stteps
1. Upgrade Workstation and Automation Server to latest available version (SBO 1.8.1.3600)
2. Connect with Workstation to Automation Server
3. Select Server, right click Advanced | Repair LonWorks configuration ...
4. Select Next to repaire when indicated "Server needs to be repaired"
5. Finally upgrade to Version 1.9 using Device Administrator

Schneider Electric Slovakia

Príloha(-y)
Start repair.PNG.png [120.18 KB]
repair01.PNG.png [37.8 KB]
Objavte viac
Rad:
Objavte viac
Rad:
  • Produktová dokumentácia
  • Prevzatia softvéru
  • Nástroj pre výber produktov
  • Nahradenie a výmena produktu
  • Centrum nápovedy
  • Nájdite naše pobočky
  • Kde kúpiť
  • Komunita Schneider Electric
  • Kariéra
  • Profil spoločnosti
  • Nahlásiť pochybenie
  • Dostupnosť
  • Redakcia
  • Investori
  • EcoStruxure
  • Vyhľadať pracovné miesta
  • Blog
  • Zásady ochrany osobných údajov
  • Upozornenie o súboroch cookie
  • Zmluvné podmienky
  • Zmeniť nastavenia cookie