What is the thickness of the Steel sheet metal used in Okken switchboard.

The Steel sheet metal thickness used in Okken switchboard is as listed below: Okken Steel sheet metal thickness Housing Thickness mm Door 2.00mm Rear panels 1.50mm Side panels 1.50mm Roof 1.50mm...

Can we cut the Neutral cable of RCBO or not ? (new product called rocket)

Yes, you can. It makes convenience and safety for wiring in Consumer unit or Load Center. And new product called rocket has straight cable also.

Can RCCB type B use with DC voltage?

For RCCB, we do not have a full-DC operated RCCB. the RCCB B type cannot be used in DC distribution network. This device is for distribution network with frequency 50 Hz. As it is Type B, it protects...

What is the material composition of the Main Bus Bar of the Masterpact ACB?

The material composition used in the Main Bus Bar of the Masterpact Air Circuit breaker (ACB) is shown in the table attached. Note: AL/Sn5 means Aluminum connector with Sn5 coated

What is the accuracy of the Premium PLC CPU real time clock.

Real time clock accuracy: Accuracy of the real time clock is one second (%SW50) +/- 200ms. Resolution of the real time clock is one second (%SW50) +/- 200ms,because 200ms is the refresh rate of the...

What is the short circuit current rating for TeSys GV2G Comb Busbar.

The short-circuit current withstand rating (KA) of Tesys Comb Busbar is compatible with the breaking capacity of Motor Protection Circuit Breakers (MPCB) of GV series. The GV Series Comb Busbar does...

What is the difference between ModSoft PID function and Concept PID...

The difference between ModSoft PID and Concept PID loops are as follows: PID (ModSoft): PB - Gain = 100 / PB I - Integral Coefficient Expressed as Repeats/Minute. The higher the value, the greater...

What is the meaning of elapsed time and power on time in the fault history...

In fault history the elapsed time refers to [Run time] (rtH). This parameter provides the total duration of time, the motor has been switched on. Power on time refers to (PtH) and this parameter...

Popular Video FAQsPopular Videos

video-thumbnail
video-thumbnail
video-thumbnail
video-thumbnail
video-thumbnail
video-thumbnail
video-thumbnail
video-thumbnail
video-thumbnail

Learn more through our Generic Knowledge FAQsGeneral Knowledge

What is the selection criterion of Circuit Breakers for the Capacitor bank...

The selection should be done after derating the Circuit Breaker taking into consideration voltage variation and capacitors tolerances that could increase nominal current up to 1.5In. The Derating...