PM5111 Meter, modbus, up to 15th H, 1DO 33 alarms, MID

Show more characteristics >
Add to My Products Remove from My Products
The maximum number of products that can be compared is 4

  • Main
    range
    PowerLogic
    product name
    PowerLogic PM5000
    device short name
    PM5111
    product or component type
    Power meter
    Complementary
    power quality analysis
    up to the 15th harmonic
    device application
    Power monitoring
    type of measurement
    Current
    Voltage
    Frequency
    Power factor
    Energy
    Active and reactive power
    supply voltage
    100...415 V AC 45...65 Hz
    125...250 V DC
    network frequency
    50 Hz
    60 Hz
    [In] rated current
    5 A
    1 A
    type of network
    3P
    1P + N
    3P + N
    ride-through time
    80 ms 120 V AC typical
    100 ms 230 V AC typical
    100 ms 415 V AC typical
    display type
    Backlit LCD
    display resolution
    128 x 128 pixels
    sampling rate
    64 samples/cycle
    measurement current
    10…9000 mA
    analogue input type
    voltage (impedance 5 MOhm)
    current (impedance 0.3 MOhm)
    measurement voltage
    35…690 V AC 45...65 Hz between phases
    20…400 V AC 45...65 Hz between phase and neutral
    frequency measurement range
    45…65 Hz
    number of inputs
    0
    measurement accuracy
    Active energy +/- 0.5 %
    Reactive energy +/- 2 %
    Active power +/- 0.5 %
    Apparent power +/- 0.5 %
    Frequency +/- 0.05 %
    Power factor +/- 0.005 %
    Current +/- 0.5 %
    Voltage +/- 0.5 %
    accuracy class
    Class 0.5S active energy conforming to IEC 62053-22
    number of outputs
    1 digital
    communication port protocol
    Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires, insulation 2500 V
    JBUS
    communication port support
    RS485
    data recording
    Time stamping
    Min/max of instantaneous values
    connections - terminals
    Voltage circuit: screw terminal block4
    Control circuit: screw terminal block2
    Current transformer: screw terminal block6
    Input/output circuit: screw terminal block6
    RS485 link: screw terminal block4
    mounting mode
    Flush-mounted
    mounting support
    Framework
    standards
    IEC 61557-12
    EN 50470-1
    UL 61010-1
    IEC 62053-24
    IEC 60529
    EN 50470-3
    IEC 62053-22
    product certifications
    CE conforming to IEC 61010-1
    CULus conforming to UL 61010-1
    MID conforming to EN 50470-1
    MID conforming to EN 50470-3
    width
    96 mm
    depth
    72 mm
    height
    96 mm
    product weight
    380 g
    Environment
    electromagnetic compatibility
    Limits for harmonic current emissionsclass A conforming to IEC 61000-3-2
    Electrostatic dischargelevel 4 conforming to IEC 61000-4-2
    Conducted RF disturbanceslevel 3 conforming to IEC 61000-4-6
    Magnetic field at power frequencylevel 4 conforming to IEC 61000-4-8
    Conducted and radiated emissionsclass B conforming to EN 55022
    IP degree of protection
    Front: IP52 conforming to IEC 60529
    Body: IP30 conforming to IEC 60529
    relative humidity
    5…95 % at 50 °C
    pollution degree
    2
    ambient air temperature for operation
    -25…70 °C
    ambient air temperature for storage
    -40…85 °C
    operating altitude
    2000 m
    compatibility code
    PM5111
    Offer Sustainability
    Sustainable offer status
    Green Premium product
    REACh Regulation
    REACh free of SVHC
    Yes
    EU RoHS Directive
    Pro-active compliance (Product out of EU RoHS legal scope)
    EU RoHS Declaration
    Mercury free
    Yes
    RoHS exemption information
    China RoHS Regulation
    Environmental Disclosure
    Circularity Profile
    WEEE
    The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
  • Documents and Downloads

    Language
    • English
    • Spanish
    • Portuguese
    • Russian
    • French
    • Italian
    • German
    • Chinese
    Catalogue
    Date
    Size
    Add to My Documents
    Catalogue for Panel Builders - Web Version (Version 3.0)
    PowerLogic Catalog - 272 pages Web (NO PRINTED VERSION AVAILABLE) (Version 8.1)
    PowerLogic Catalogue - 272 pages - Print File (NO PRINTED VERSION AVAILABLE) (Version 8.2)
    Catalogue for Panel Builders - Print Version (Version 3.0)
    User guide
    Date
    Size
    Add to My Documents
    PowerLogic PM5100 Series User Manual - EN (Version 05)
    CAD
    Date
    Size
    Add to My Documents
    PowerLogic PM51101Power & Energy meters, Cl 0.5, RS-485 Modbus, MID (Version 1.0)
    CAD files for METSEPM5111: Powerlogic PM5100 (Version 1.0)
    Instruction sheet
    Date
    Size
    Add to My Documents
    PowerLogic PM5100 Series Installation Guide (Version 8)
    Declaration of conformity
    Date
    Size
    Add to My Documents
    CE mark for PM5000 MID meters (Version 1.0)
    Date 5/10/16
    Size 643.2 KB
    EU RoHS Declaration
    Date
    Size
    Add to My Documents
    Date 7/23/19
    Size 195.3 KB
    Firmware - Released
    Date
    Size
    Add to My Documents
    PM51xx (PM5110,5111,) Firmware V1.5.4 and V1.6.4 and associated files - Register List, Revision History (Version 1.0)
    PM51xx (PM5110,5111,) Firmware V2.1.1 and V2.2.1 and associated files - Register List, Revision History (Version 1.2)
    REACh Declaration
    Date
    Size
    Add to My Documents
    Date 7/23/19
    Size 195.3 KB
    Technical leaflet
    Date
    Size
    Add to My Documents
    PM5000 Technical Datasheet - Web Version (Version 3.4)
  • Technical FAQs

    No results found.
    Unfortunately, related FAQs are unavailable due to temporary technical issues. Please try again later.