How can the ATS48 soft starter be set up to run a small motor for testing?
Issue:
ATS48 setup to run a small motor for testing
Product Line:
ATS48
Environment:
Cause:
Resolution:
From the DRC menu set the SSt parameter to On.
Use this parameter to check the soft starter in a testing or maintenance environment, on a motor whose power is very much lower than the soft starter rating (in particular for high power soft starters).
It automatically deactivates the torque control parameter, CLP.
OFF: function inactive
On: function active
SSt returns to the OFF state as soon as the control voltage is disconnected. On the next power up, the PHF fault and the CLP parameter return to their initial configuration.
ATS48 setup to run a small motor for testing
Product Line:
ATS48
Environment:
Cause:
Resolution:
From the DRC menu set the SSt parameter to On.
Use this parameter to check the soft starter in a testing or maintenance environment, on a motor whose power is very much lower than the soft starter rating (in particular for high power soft starters).
It automatically deactivates the torque control parameter, CLP.
OFF: function inactive
On: function active
SSt returns to the OFF state as soon as the control voltage is disconnected. On the next power up, the PHF fault and the CLP parameter return to their initial configuration.
เผยแพร่สำหรับ: ชไนเดอร์ อิเล็คทริค Thailand


ต้องการความช่วยเหลือใช่หรือไม่
โปรแกรมช่วยเลือกผลิตภัณฑ์
ค้นหาผลิตภัณฑ์และอุปกรณ์เสริมที่เหมาะสมกับการใช้งานของคุณได้อย่างรวดเร็วและง่ายดาย
ติดต่อฝ่ายขาย
ติดต่อสอบถามเกี่ยวกับการขายผ่านทางเว็บไซต์ และผู้เชี่ยวชาญจะติดต่อกลับ
สถานที่จัดจำหน่ายอยู่ที่ใด
ค้นหาตัวแทนจำหน่าย ชไนเดอร์ อิเล็คทริค ที่ใกล้ตัวคุณที่สุดได้อย่างง่ายดาย
ศูนย์ความช่วยเหลือ
ค้นหาแหล่งข้อมูลเพื่อสนับสนุนความต้องการทั้งหมดของคุณได้จากที่เดียว